Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 340 VAC (3~ + PE)
Rated Current 100 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 45 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 20 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Heavy-Duty Screw Terminals
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for effective shielding and heat dissipation
Category Parameter Specification / Typical Value
Contactor (S801) Rated Operational Current (Ie) 32 A at AC-3, 400V
Utilisation Category AC-3: Squirrel cage motors (Starting, switching off)
AC-1: Non-inductive loads
Rated Thermal Current (Ith) 40 A
Motor Rating at 400V AC 15 kW / 20 HP (Approx.)
Coil Control Voltage Must be specified separately (e.g., 24V AC/DC, 110V AC, 230V AC, etc.)
Mechanical Life > 10,000,000 cycles
Electrical Life (AC-3) > 1,000,000 cycles
Auxiliary Contact (T24N3S) Contact Configuration 3 NO (Three Normally Open Contacts)
Rated Current Typically 6 A
Utilisation Category AC-15: Control of electromagnetic loads (e.g., relays, contactor coils)
General Data Number of Main Poles 3
Mounting 35 mm DIN Rail
Connection Type Screw Terminals
Standards IEC/EN 60947-4-1, UL 508
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 342 VAC (3~ + PE)
Rated Current 55 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 45 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 10 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for effective shielding and heat dissipation
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 342 VAC (3~ + PE)
Rated Current 81 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 45 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 15 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for effective shielding and heat dissipation
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 340 VAC (3~ + PE)
Rated Current 55 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 45 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 10 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for effective shielding and heat dissipation
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 340 VAC (3~ + PE)
Rated Current 55 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 60 dB (Typical at 1 MHz)
> 45 dB (Typical at 100 kHz)
Leakage Current Line to Ground Typically < 10 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals
Mounting Through-hole or bracket mounting (panel mount)
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum) for effective shielding and heat dissipation
Category Parameter Specification / Typical Value
Electrical Ratings Rated Voltage 340 VAC (3~ + PE)
Rated Current 32 A
Frequency 50/60 Hz
Test Standards Safety Standards UL 60939, IEC 60939, EN 60939
EMC Standards Designed to meet CISPR 11/32, EN 55011/55032
Filter Performance Insertion Loss > 50 dB (Typical at 1 MHz)
Leakage Current Line to Ground Typically < 5 mA (per phase)
General Data Number of Phases 3-Phase + Protective Earth (PE)
Connection Type Screw Terminals
Mounting Through-hole or bracket mounting
Operating Temperature -25 °C to +100 °C
Housing Material Metal case (typically aluminum)
Category Parameter Specification / Typical Value
Motor Protection Setting Current Range (Iᵣ) 0.63 - 1 A (This is the core protective range)
Tripping Class 10A (Standard tripping time: < 10 sec at 7.2 x Iᵣ)
Ambient Temperature Compensation Yes, for stable performance across a range of temperatures
Electrical Characteristics Rated Operational Voltage (Uᵢ) Up to 690 V AC
Utilisation Category AC-3: Squirrel cage motors
Contacts Control Circuit Contacts 1 NO (97-98) - Fault Signal
1 NC (95-96) - Fault Signal
Rated Thermal Current (Iᵗʰ) 9 A
General Data Mounting Snap-on to compatible Eaton contactors (e.g., DILM series)
Reset Mode Manual reset (Standard for safety after a trip)
Status Indication Mechanical flag for trip indication
Standards IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Category Parameter Specification / Typical Value
Motor Protection Setting Current Range (Iᵣ) 0.15 - 0.24 A (This is the core protective range)
Tripping Class 10A (Standard tripping time)
Ambient Temperature Compensation Yes
Electrical Characteristics Rated Operational Voltage (Uᵢ) Up to 690 V AC
Utilisation Category AC-3: Squirrel cage motors
Contacts Control Circuit Contacts 1 NO (97-98) - Fault Signal
1 NC (95-96) - Fault Signal
Rated Thermal Current (Iᵗʰ) 9 A (Frame rating)
General Data Mounting Snap-on to compatible Eaton contactors
Reset Mode Manual reset (Standard for safety after a trip)
Status Indication Mechanical flag for trip indication
Standards IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Category Parameter Specification / Typical Value
Input Characteristics Input Voltage Universal AC/DC (e.g., 24-240V AC/DC)
Input Type Typically voltage-sensing
Output Characteristics Contact Configuration 1 CO (Changeover) / SPDT
Contact Rating Typically 6A @ 250V AC / 6A @ 30V DC
Utilisation Category AC-15: Control of electromagnetic loads
DC-13: Control of DC solenoids
Isolation & Indication Isolation Reinforced insulation between input and output circuits
Status Indication LED to indicate when the input is energized and the output is active
General Data Mounting 35 mm DIN Rail
Connection Type Screw terminals or spring-cage terminals (depending on version)
Operating Temperature -25 °C to +60 °C
Standards IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14