Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, P1 Series (Domae)
Model Number P1-25/I2/SVB25A
Rated Current (In) 25 A
Number of Poles 1-Pole
Rated Operational Voltage (Ue) 230V AC (Single-Phase)
Rated Insulation Voltage (Ui) 400V AC
Breaking Capacity (Icn) Typically 6 kA / 10 kA (Please confirm with specific catalog)
Tripping Characteristic Type C (Instantaneous trip: 5-10 x In)
Auxiliary Contact I2 - Auxiliary Contact Configuration (e.g., 1 Normally Open (NO) contact for remote signaling)
Terminal Type SVB - Shrouded Terminal Barrier (Finger Protection)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60898-1
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, MFD Series
Model Number MFD-CP4
Power Supply Voltage 24V DC (Typical for "C" variant)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.1 seconds up to 100 hours)
Functions Multiple timing functions selectable (e.g., On-delay, Off-delay, Interval, Flasher, etc.)
Accuracy ±0.5% of set time ± 20 ms
Mounting DIN Rail (35mm)
Display / Indication Digital Display and LED Status Indicators
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, MFD Series
Model Number MFD-80-B
Power Supply Voltage 24-240V AC/DC (Wide range, auto-sensing)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.1 seconds up to 100 hours)
Functions Multiple timing functions selectable (e.g., On-delay, Off-delay, Interval, Flasher, etc.)
Accuracy ±0.5% of set time ± 20 ms
Mounting DIN Rail (35mm)
Display / Indication Digital Display and LED Status Indicators
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, EASY600 Series
Model Number EASY620-DC-TE
Power Supply 24V DC
Digital Inputs 12 (24V DC, sink/source)
Digital Outputs 8 (Relay outputs)
Integrated Expansion Yes (TE - Totally Enclosed design with additional I/O)
Program Memory ~1 KB (typical for EASY600 series)
Mounting DIN Rail (35mm)
Programming EASY-SOFT software or front-panel display
Communication Optional communication interfaces
Standards Compliance IEC/EN 61131-2, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, MFD Series
Model Number MFD-RA17
Power Supply Voltage 24-240V AC/DC (Wide range, auto-sensing - typical for MFD series)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.1 seconds up to 100 hours)
Functions Specific timing functions defined by the RA17 code (e.g., a particular combination of On-delay, Off-delay, Interval, etc.)
Accuracy ±0.5% of set time ± 20 ms
Mounting DIN Rail (35mm)
Display / Indication Digital Display and LED Status Indicators
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, FAZ Series (Bussmann)
Model Number FAZ-B32/1
Fuse Class & Rating Class B
Rated Current: 32 A
Rated Voltage: 600V AC / 300V DC
Number of Poles / Quantity 1 piece (Single fuse)
Type Time-Delay (Dual-Element)
Rated Voltage 600V AC / 300V DC
Interrupting Rating 200 kA AC (200,000 Amps) at 600V AC
Approvals / Standards UL 248-12 (Class B), CSA C22.2 No. 248.12
Electrical Characteristics Current-Limiting: Yes
Time-Delay: Can withstand 500% of rated current for several seconds.
Physical Dimensions Body: 13/32" x 1-1/2" (10.3mm diameter x 38.1mm length)
Mounting / Fuse Holder Requires a compatible Class B fuse holder or fuse block
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, MFD Series
Model Number MFD-R16
Power Supply Voltage 24-240V AC/DC (Wide range, auto-sensing - typical for MFD series)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.1 seconds up to 100 hours)
Functions Specific timing functions defined by the R16 code (e.g., a particular combination of On-delay, Off-delay, Interval, etc.)
Accuracy ±0.5% of set time ± 20 ms
Mounting DIN Rail (35mm)
Display / Indication Digital Display and LED Status Indicators
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILER Series
Model Number DILER-31
Rated Operational Current (Ie) 6 A (for AC-15 category, 250V AC)
Poles 4-Pole (Typically 4 Changeover (CO) contacts)
Contact Configuration 4 CO (4 Changeover contacts - 4 NO + 4 NC)
Rated Operational Voltage (Ue) Up to 250V AC / 300V DC
Control Coil Voltage Available in multiple standard AC and DC voltages (e.g., 24V, 110V, 230V AC/DC). The specific voltage is not defined by "31" and must be specified when ordering.
Utilization Categories AC-15: Control of electromagnetic loads (≤ 720 VA)
DC-13: Control of electromagnetic loads
Mechanical Life ~ 10 - 30 million operations
Electrical Life Varies by utilization category (e.g., ~ 1-3 million operations at rated AC-15 load)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60947-5-1
Terminal Type Cage Clamp or Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILER Series
Model Number DILER-22-G
Rated Operational Current (Ie) 6 A (for AC-15 category, 250V AC)
Poles 2-Pole
Contact Configuration 2 CO (2 Changeover contacts - 2 NO + 2 NC)
Rated Operational Voltage (Ue) Up to 250V AC / 300V DC
Control Coil Voltage Available in multiple standard AC and DC voltages (e.g., 24V, 110V, 230V AC/DC). The specific voltage must be specified when ordering.
Utilization Categories AC-15: Control of electromagnetic loads (≤ 720 VA)
DC-13: Control of electromagnetic loads
Mechanical Life ~ 10 - 30 million operations
Electrical Life Varies by utilization category (e.g., ~ 1-3 million operations at rated AC-15 load)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60947-5-1
Terminal Type Cage Clamp or Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILM Series
Model Number DILM80-11N
Rated Operational Current (Ie) 80 A at AC-3, 400V
Thermal Current (Ith) 80 A
Poles (Main Circuit) 3 (Normally Open)
Auxiliary Contacts 1 NO (Normally Open) + 1 NC (Normally Closed) - Convertible
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage AC operating coil (Specific voltage must be specified when ordering, e.g., 230V AC).
Utilization Categories AC-3: Squirrel cage motors: Starting, switching off during running
AC-1: Non-inductive or slightly inductive loads
Motor Rating (at 400V AC) 37 kW / 50 HP
Mechanical Life ~ 10 million operations
Electrical Life (AC-3) ~ 1 million operations
Mounting Standard 35mm DIN Rail (EN 60715) or screw mounting
Standards Compliance IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Terminal Type Screw Clamp