Model Foxboro IAP10-A22E3F-L2Z1 Type Electropneumatic Transducer (I/P) Input Signal 4-20 mA DC, 2-wire (loop powered) Output Pressure 3-15 psi (0.2 - 1.0 bar) Air Supply Pressure 20-55 psi (1.4 - 3.8 bar) - Clean, dry air required Accuracy ±0.5% of span (typical for standard calibration) Linearity ±0.5% of span Hysteresis < 0.1% of span Supply Air Consumption Typically < 0.2 SCFM (5.7 SLPM) at no flow Enclosure Rating General Purpose (Not explosion-proof). Typically NEMA 1 or NEMA 4X fiberglass enclosure. Conduit Connection 1/2" NPT Process Connection 1/4" NPT for air supply and output ports Wetted Materials Anodized aluminum, Nitrile (Buna-N) seals (standard). Other materials like Stainless Steel available in other models. Ambient Temperature -20°C to +80°C (-4°F to +176°F) Relative Humidity 0-95% (non-condensing)