Parameter Specification Product Model MTL4523 Product Line Eaton MTL Signal Conditioners & Isolators Function Single-channel, 2-Wire Transmitter Isolator & Power Supply Input Signal Accepts and powers a 2-wire, 4-20 mA transmitter from a hazardous area. Output Signal Isolated 4-20 mA DC signal. Input/Output Isolation Galvanic Isolation between input, output, and power supply. Power Supply Typically 20-30 V DC Intrinsic Safety (IS) Approval Yes. Certified for use in Hazardous Areas (e.g., ATEX, IECEx). Entity Parameters (Example values, MUST be verified for design): - Vmax (Ui): e.g., 28 V - Imax (Ii): e.g., 93 mA - Pi: e.g., 0.65 W - Ci: e.g., 0 μF - Li: e.g., 0 mH Non-Incendive (NI) Approval Yes (for applicable standards like FM/CSA). Line Fault Detection Yes, can detect open and short circuits in the field wiring. Accuracy Typically better than ±0.1% of span. Mounting DIN-Rail Mount (Standard 35 mm) Operating Temperature -20°C to +60°C Compliance & Certifications ATEX, IECEx, FM, CSA, NEPSI, etc. (Specific certifications depend on the product suffix).