Parameter Specification Product Series Eaton DS7 / XStart Model Number DS7-340SX007N0-N Description Soft Starter, 34A, 15kW @ 400V Rated Supply Voltage 400V AC, 50/60 Hz Motor Power Rating 15 kW / 20 HP @ 400V Rated Current 34 A Current Range 5 - 34 A (Adjustable) Max. Current 150 A (for 1 second) Control Method Voltage Ramp, Current Limit Integrated Bypass Yes (Internal Bypass Contactor) Control Voltage 100-250V AC, 50/60 Hz (from factory, as denoted by 'SX') Control Connections Screw Terminals Start Time Adjustment 1 - 30 seconds (Adjustable) Torque Control Adjustable Initial Torque (Kickstart) and Torque Limit Protection Features Overload, Phase Loss, Phase Imbalance, Locked Rotor, Overheating, Jogging Protection Status Indication LED Indicators for Power, Run, Bypass, Fault Communication Optional communication modules (e.g., Profibus, DeviceNet) available Enclosure Rating IP00 (Open Type, must be installed in a control panel for protection) Standards & Certifications CE, UL, cUL, RoHS