Parameter Specification Product Series PLHT Brand Eaton Product Type Miniature Circuit Breaker (MCB) Number of Poles 3 Poles (3P) Rated Current (In) 125 A Tripping Characteristic C Curve (Instantaneous trip current: 5 to 10 times In) Rated Operational Voltage (Ue) 400 V / 415 V ~ Rated Insulation Voltage (Ui) 500 V ~ Rated Impulse Withstand Voltage (Uimp) 6 kV Rated Breaking Capacity (Icn) 10 kA / 15 kA (at 400/415V AC) Please check the specific datasheet for the confirmed value. Utilization Category A Standards IEC/EN 60898-1, IEC/EN 60947-2 Electrical Life 10,000 cycles Mechanical Life 20,000 cycles Terminal Torque 3.5 - 4.0 N·m (For larger cable sizes, please confirm with datasheet) Mounting DIN Rail Mounting (35mm symmetrical rail according to EN 60715) Net Weight Approx. 0.7 kg (May vary)