Technical Parameters Parameter Category Specification / Value Brand Eaton Product Series PXK Product Model PXK-B16/1N/003-A Product Type Type 2 / Class II Surge Protective Device (SPD) Rated Voltage (Uc) 230/400 V AC Nominal System Voltage 230 V AC (Single-Phase + N) Protection Mode 1-Pole + N (L-PE, N-PE) Max. Discharge Current (Imax - 8/20 µs) 16 kA per mode Nominal Discharge Current (In - 8/20 µs) 8 kA Voltage Protection Level (Up) ≤ 1.5 kV Response Time < 25 ns Backup Overcurrent Protection (Recommended) 16 A to 63 A gG/gL (or per local regulations) Status Indication Visual Indicator (Green: OK; Red: End-of-Life) Remote Signalling Contact 1 Changeover Contact (SPDT) Mounting 35 mm DIN Rail (EN 60715) Connection Screw Terminal Approvals / Certifications CE, IEC 61643-11