Technical Parameters Parameter Category Specification Details General Model DILM40-11N DILM Series, 40A, Standard Design Product Line Eaton DILM Contactors Main Contact Characteristics Rated Operational Current (Ie) 40 A (at AC-3, 400V) Rated Thermal Current (Ith) 55 A Rated Insulation Voltage (Ui) 690 V Rated Operational Voltage (Ue) Up to 690V AC Motor Power Rating (AC-3) 22 kW (30 HP) @ 400V AC Poles 3 (Main Poles) Coil Characteristics Coil Voltage 24V DC Power Consumption Approx. 8 W (DC) Pick-up Voltage Typically 80-110% of rated voltage Mechanical Characteristics Electrical Durability Typically > 1 million operations (at rated current) Mechanical Durability Typically > 10 million operations Mounting Standard 35mm DIN Rail or screw mounting Auxiliary Contacts Standard Configuration Typically 1 Normally Open (NO) auxiliary contact Expandable Yes, with additional auxiliary contact blocks Standards & Compliance Safety Standards UL 508, CSA C22.2 No. 14, IEC/EN 60947-4-1