Parameter Description Specification / Note Product Series DILM Eaton's series for contactors and contactor relays. Product Generation A Denotes the enhanced "A" version, offering improved electrical endurance. Rated Operational Current (Ie) AC-1 (Resistive Load) 22 A at 690V (This is the core current rating of the main contacts). Rated Operational Power (P_e) AC-3 (Squirrel Cage Motor) 7.5 kW at 400V / 50 Hz. AC-1 (Resistive Load) 15 kW at 400V. Poles Main Circuits 4 Poles (4 NO - Normally Open) Rated Insulation Voltage (U_i) 1000 V Rated Operational Voltage (U_e) Up to 690 V AC Coil Control Voltage The "22" in the part number indicates a specific AC coil voltage. Commonly: 230V AC, 50/60 Hz. (It is essential to verify the specific voltage from the coil label or official datasheet, as other standard voltages like 24V, 110V, and 400V are available). Accessory / Option RAC240 Integrated AC Coil Suppression Module. This accessory is optimized for use with AC coils, helping to reduce electrical noise and improve performance in AC control circuits. Electrical Durability AC-3 (at rated operational current) Typically > 2 million operations (a key improvement in the "A" version). Mechanical Durability Typically > 15 million operations. Mounting Standard 35 mm DIN rail (EN 60715). Connection Cage clamp (spring-loaded) terminals for fast, secure, and tool-free wiring. Standards & Approvals CE, cULus (UL 508), CCC, IEC/EN 60947-4-1, etc.