T0-2-15679/11/SVB

Category Parameter Specification Application Protected Circuit 2-wire Analog signals (e.g., 4-20 mA loops) Connection In-series with the signal line Electrical Characteristics Nominal Voltage 8 V DC Max. Continuous Operating Voltage Uc 12 V DC Nominal Current ≤ 250 mA Voltage Drop Typically < 1 V Insertion Loss Typically negligible Surge Protection Performance Test Waveform (IEC 61643-21) 1.2/50 μs (Voltage) - 8/20 μs (Current) Nominal Discharge Current (In) 5 kA (8/20 μs) Max. Discharge Current (Imax) 10 kA (8/20 μs) Protection Level (Up) < 25 V (at In = 5 kA, 8/20 μs) General Data Number of Poles / Channels 2 (for series connection in one signal loop) Connection Type Screw terminals Mounting 35 mm DIN Rail Housing Material Plastic Operating Temperature -40 °C to +80 °C Standards / Approvals IEC 61643-21, CE

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
The Eaton T0-2-15679/11/SVB is a compact, two-pole surge protection device (SPD) designed to protect sensitive 4-20 mA analog signal lines from transient overvoltages induced by lightning strikes, electrostatic discharge, or electromagnetic interference in industrial environments. It is mounted on a standard DIN rail within a control cabinet and wired in series with the signal loop to provide reliable protection for both the field device (e.g., sensor/transmitter) and the control system input (e.g., PLC/DCS analog input card).