Category Parameter Specification / Typical Value Motor Protection Setting Current Range (Iᵣ) 0.06 - 0.6 A (This is the core protective range) Tripping Class 10 (Standard) / 20 (e.g., for high-inertia loads) - Selectable Protection Functions • Overload • Phase Loss / Unbalance • Jam Protection (with adjustable trip time) • Earth Fault Protection (optional, depends on version) Electrical Characteristics Rated Operational Voltage (Uᵢ) Up to 690 V AC Supply Voltage (for electronics) Typically 24-240 V AC/DC (Auxiliary voltage for the relay's own circuitry) Contacts Output Auxiliary Contacts • 1 NO (95-96) - Fault Signal • 1 NC (97-98) - Fault Signal Rated Current of Aux. Contacts Typically 6 A General Data Mounting Snap-on to compatible Eaton contactors (e.g., DILM series) Standards IEC/EN 60947-4-1, UL 508 Status Indication LED indicators for "Ready", "Alarm/Trip" Ambient Temperature -20 °C to +60 °C