Technical Specifications Parameter Specification / Typical Value Manufacturer / Brand Eaton Model Number PKZM0-25 Product Line PKZ (Moeller Series) Rated Operational Current for Motors (Ie) 25 A (Max) Setting Range for Thermal Overload Approx. 18 - 25 A (adjustable via a dial) Poles (Main Circuit) 3 Rated Operational Voltage (Ue) 690 V AC Rated Insulation Voltage (Ui) 690 V / 750 V AC Rated Ultimate Breaking Capacity (Icu/@400V) Typically 50 kA or 100 kA (Must be verified from the official datasheet) Tripping Class Class 10 (Standard for general motors, trips within 10 seconds at 7.2 x Ir) Short-Circuit Protection Setting Fixed, based on the device design (typically around 12 x Ie or higher) Auxiliary Contacts Can typically be fitted with one or more auxiliary contact modules (e.g., PKZM0-1X) to signal the trip status. Mounting DIN Rail Mount (35mm) Standards Compliance IEC/EN 60947-2, IEC/EN 60947-4-1