Parameter Specification Model MR95H Product Line Fisher MR Series I/P Converter Device Type Current-to-Pressure (I/P) Converter Input Signal 4-20 mA DC (Standard two-wire) Output Pressure Range Standard: 3-15 psig (0.2-1.0 bar) Other Ranges: Available, such as 3-27 psig, 6-30 psig. Supply Pressure 20 psig (1.4 bar) minimum, 40 psig (2.8 bar) typical, up to 120 psig (8.3 bar) maximum. Must be at least 3-5 psi above the required output pressure. Air Consumption Static (No Signal): Typically ≤ 0.2 scfm (0.0057 Nm³/min) Dynamic (With Signal): Varies with output. Accuracy Typically ±0.5% of span (including linearity, hysteresis, and dead band) Supply Connection 1/4 in. NPT (F) Output Connection 1/4 in. NPT (F) Mounting Standard: Panel mount (for 1-1/8 in. or 29mm diameter hole) Optional: Manifold mount, surface mount, or 35mm DIN rail kit. Enclosure Rating NEMA 4X (IP66) when properly mounted. Material Aluminum enclosure with polyurethane coating. Ambient Temperature Range -20° to 180°F (-29° to 82°C)