Technical Parameters Parameter Specification Model / Assembly DVC6200 (W30382X0012) Input Signal 4-20 mA DC, with HART 5/7/ protocol Supply Air Pressure 20 to 150 psi (1.4 to 10.3 bar) - Actuator Dependent Air Consumption (Quiescent) Typically < 0.14 SCFM (0.23 Nm³/hr) Enclosure Rating NEMA 4X / IP66/67 Ambient Temperature Range -40° to 185°F (-40° to 85°C) Travel Range Actuator Dependent. This is a critical parameter defined by the specific actuator in the assembly. Line Size / Valve Type Actuator and Valve Dependent. Defined by the complete assembly. Mounting Directly on linear or rotary actuators (Pre-assembled unit)