Technical Parameters Category Parameter Specification / Description General Base Model DVC6205 Output Module 6215HC (High-Capacity) Product Family FIELDVUE Primary Protocol HART Input & Control Input Signal 4 to 20 mA DC, two-wire Supply Pressure Up to 150 psig (10.3 bar) Performance (HC Output) Output Capacity Supply/Exhaust Flow: Up to 160 SCFM (4531 NLPM). This is the key differentiator, significantly higher than standard models. Steady-State Air Consumption ~0.04 SCFM (1.1 NLPM) Linearity ±0.5% of span (default) Hysteresis Less than 0.3% of span Environmental Ambient Temperature -40°F to 185°F (-40°C to 85°C) Enclosure Rating Type 4X, 6 (IP66/67); Dust-tight and protected against water. Hazardous Area Certifications FM/CSA: Explosion-proof, Intrinsically Safe (Class I, II, III, Div. 1 & 2) ATEX/IECEx: Ex db, Ex tb, Ex ia [ia] (Zone 1 & 21) Physical Conduit Openings Two 1/2" NPT Pneumatic Connections Supply & Output: 1/2" NPT or 3/4" NPT (for high flow)