Technical Parameters Category Parameter Specification / Description General Model DVC6200HC Type Digital Valve Controller (High Capacity) Product Family FIELDVUE Primary Protocol HART Input & Output Input Signal 4 to 20 mA DC, two-wire Supply Pressure Up to 150 psig (10.3 bar) Performance (HC Output) Output Capacity Supply/Exhaust Flow: Up to 160 SCFM (4531 NLPM). This is the key specification, significantly higher than standard models (~40 SCFM). Steady-State Air Consumption ~0.04 SCFM (1.1 NLPM) Linearity ±0.5% of span Hysteresis Less than 0.3% of span Environmental Ambient Temperature -40°F to 185°F (-40°C to 85°C) Enclosure Rating Type 4X, 6 (IP66/67); Dust-tight and protected against water. Hazardous Area Certifications FM/CSA & ATEX/IECEx: Explosion-proof, Intrinsically Safe approvals for hazardous areas. Physical Conduit Openings Two 1/2" NPT Pneumatic Connections Supply & Output: Typically 1/2" NPT or 3/4" NPT to accommodate the high flow.