Products
Products
home
FISHER 6392

Technical Parameters Category Parameter Specification / Description General Model 6392 Type Electro-Pneumatic Transducer (I/P) Input & Output Input Signal 4 to 20 mA DC, two-wire Output Signal 3 to 15 psig (0.2 to 1.0 bar) Supply Pressure 20 psig (1.4 bar) minimum, 20-35 psig (1.4-2.4 bar) typical. Must be at least 3-5 psi above desired output. Performance Accuracy ±0.5% of span Linearity & Hysteresis ±0.5% of span (combined) Air Consumption Steady State: ~0.15 SCFM (4.2 NLPM) Load Capacity Can drive light loads directly. For high-volume devices (like large actuators), a booster relay may be required. Environmental Ambient Temperature -40°F to 175°F (-40°C to 80°C) Enclosure Rating Type 4X, 7, 9 (NEMA 4X, 7, 9); Weatherproof, dust-tight, and certified for hazardous locations. Hazardous Area Certifications FM/CSA: Intrinsically Safe and Explosion-proof approvals. Physical Housing Material Aluminum Pneumatic Connections 1/4" NPT Conduit Opening 1/2" NPT

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
The Fisher 6392 is an electro-pneumatic transducer, commonly known as an I/P (Current-to-Pressure) transducer. Its primary function is to convert a standard analog electronic control signal (4-20 mA) into a precisely proportional pneumatic output signal (3-15 psig).