Technical Specifications Category Specification Type Electro-Pneumatic Transducer (I/P) Input Signal 4-20 mA DC (reverse acting) Output Signal 3-15 psig (0.2-1.0 bar) Supply Pressure 20-150 psig (1.4-10.3 bar) Accuracy ±0.5% of span Linearity ±0.5% of span Hysteresis ±0.1% of span Air Consumption < 0.2 SCFM at steady state Enclosure Rating NEMA 4X Temperature Range -40°F to 180°F (-40°C to 82°C) Mounting 2-inch pipe mounting or surface mounting Typical Applications Control Valve Positioning Pneumatic Actuator Control Process Control Systems DCS and PLC Interface Pneumatic Instrumentation Systems Reverse Acting Control Applications