Technical Specifications Category H284 (P/P Transducer) H5114 (I/P Transducer) Type Pneumatic-to-Pneumatic Electro-Pneumatic Input Signal 3-15 psig (0.2-1.0 bar) 4-20 mA DC Output Signal 3-15 psig (0.2-1.0 bar) 3-15 psig (0.2-1.0 bar) Supply Pressure 20-100 psig (1.4-6.9 bar) 20-150 psig (1.4-10.3 bar) Accuracy ±0.5% of span ±0.5% of span Linearity ±0.5% of span ±0.5% of span Hysteresis ±0.1% of span ±0.1% of span Air Consumption < 1.0 SCFM < 0.5 SCFM Enclosure Rating NEMA 4X NEMA 4X Temperature Range -40°F to 180°F (-40°C to 82°C) -40°F to 180°F (-40°C to 82°C) Typical Applications H284: Control valve action reversal Pneumatic signal amplification Pneumatic computing circuits Signal inversion in control systems H5114: DCS/PLC to valve interface Pneumatic actuator control Process control systems Control valve positioning Modernization projects