FISHER™ TYPE MR105

Key Parameters Category Parameter Description / Typical Values Pressure Ratings Maximum Inlet Pressure (P1) Up to 400 psig (28 bar). Monitor Setpoint Range (P2) Adjustable via its dedicated pilot. The setpoint is always set higher than the primary regulator's outlet pressure. Capacity Flow Coefficient (Cv) High Cv values, designed to handle the full system flow rate in case of a primary regulator failure. Size & Connections Pipe Size 2 inches (DN50) to 8 inches (DN200) and larger. End Connections Flanged (ANSI Class 150, 300, etc.). Materials Body Material Cast Iron or Ductile Iron. Trim Materials Stainless Steel. Pilot Pilot Type Reducing Pilot (configured for the monitor setpoint). Operation Normal State Wide Open (passive). Activation Begins throttling when outlet pressure exceeds its setpoint.

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
The Fisher™ Type MR105 is a pilot-operated, monitoring-style pressure regulator designed to provide a critical layer of safety and backup control in gas pressure reduction systems. It is not a primary regulator but acts as a "watchdog" or "monitor" in series with a primary (working) regulator. Its purpose is to take control only if the primary regulator fails or the outlet pressure rises abnormally, preventing an overpressure condition downstream.