Parameter Category Specification
System / Standard KNX / EN 50090, ISO/IEC 14543
Bus Voltage 21 – 32 V DC (KNX SELV)
Auxiliary Supply (Us) 24 V AC/DC, SELV (Typical for valve actuators and fan speed relays)
Core HVAC Control Functions • Room Temperature Control: Compares measured room temperature (via integrated or external sensor) with setpoint.
• Fan Speed Control: 3-speed (High/Med/Low) or 4-speed (including Auto) via relay outputs.
• Valve Control: Modulating control of water valves via 0-10V analog outputs for precise flow regulation in 2-pipe or 4-pipe systems.
• Operating Mode Selection: Auto, Comfort, Standby, Frost Protection, etc.
Inputs & Sensors • Integrated Room Temperature Sensor (likely due to E suffix).
• Binary Inputs (AB): For window contacts, presence detectors, local push-buttons.
• Optional External Sensors: Can connect to external temperature sensors (e.g., floor sensor) via KNX or analog input.
Outputs • Analog Outputs (AE): 2 channels of 0-10V DC for controlling heating valve and cooling valve actuators (in a 4-pipe system).
• Relay Outputs (AG): Typically 3 or 4 relays for fan speed control (High, Medium, Low, possibly Off). Each relay rated for fan motor load (e.g., 5(2)A @ 230V AC).
• Additional Auxiliary Relay: May include one for On/Off valve or summer/winter changeover.
KNX Communication • Sends room temperature, operating mode, fan speed, valve position, alarms.
• Receives setpoints, mode commands, schedules from higher-level systems.
• Can be part of energy management scenes (e.g., night setback).
User Interface Likely includes a basic local display (showing temperature/setpoint) and buttons for manual override (if E indicates this feature).
Configuration Exclusively via ABB ETS (Engineering Tool Software). Extensive parameters for: PID control loops, valve characteristics, fan speed logic, interlock with window contacts, hysteresis, etc.
Mounting 35 mm DIN Rail in a distribution board, typically located near the fan coil unit.
Typical Wiring Connects to: KNX bus, 24V AC/DC power supply, fan motor terminals, valve actuator cables, window contact, and optionally an external temperature sensor.