Technical Parameters
Parameter Category Specification
Product Series / Platform ABB Relion® 615 Series (Transformer Protection Platform)
Device Type Numerical Transformer Protection and Control Relay (IED)
Hardware Variant Suffix • -E: Wide-range auxiliary power supply (e.g., 48-250V DC / 48-240V AC).
• -1G: Specific hardware package defining the number and type of I/O modules, communication ports, and possibly analog input configurations. 1G often indicates a standard or common configuration for transformer applications.
Key Standards IEC 60255, IEC 61850 (Ed. 2), IEC 60870-5-103
Rated Auxiliary Supply (Us) 48 - 250 V DC / 48 - 240 V AC, 50/60 Hz (Auto-ranging, typical for -E).
Analog Inputs (Typical) Designed for Dual-CT Sets:
• HV Side: 3 phase currents (I1, I2, I3) + 1 neutral current.
• LV Side: 3 phase currents (I4, I5, I6) + 1 neutral/ground current.
• Configurable for 1 A or 5 A secondary.
• Voltage Inputs: 3 phase voltages (for HV or LV side metering/protection) + 1 residual voltage.
Core Protection Functions Transformer-Specific Suite:
• Differential Protection (87T): High-impedance or percentage restrained, with harmonic restraint for inrush and overexcitation.
• Restricted Earth Fault (REF) Protection (87N): For both HV and LV windings.
• Overcurrent Protection (50/51, 50N/51N): Backup protection for HV and LV sides.
• Thermal Overload Protection (49): For transformer winding and oil.
• Over/Under Voltage (27/59) & Frequency (81).
• Buchholz & Sudden Pressure Relay Interface.
• Circuit Breaker Failure (50BF).
Control & Automation • Integrated Bay Control: For HV and LV circuit breakers, isolators, and tap changers.
• Programmable Logic (CFC): Extensive logic for interlocking, sequencing, and automation.
• Voltage-based Auto-Reclosing (79) and Synchronization (25).
Measurement & Metering High-accuracy (Class 0.5) measurement of currents, voltages, power (P, Q, S), power factor, frequency, energy, and harmonics on both sides of the transformer.
Human-Machine Interface (HMI) • Large graphical LCD.
• Intuitive keypad.
• Status LEDs.
• Front USB port.
Data Recording • Event Recorder (≥ 2000 events).
• Disturbance Recorder (Multiple analog and binary channels).
Communication Interfaces As per -1G package, typically includes:
• Multiple Ethernet ports for IEC 61850-8-1 (GOOSE/MMS) and station bus.
• RS485 serial port(s) for legacy protocols (IEC 60870-5-103, Modbus RTU).
(Exact ports depend on the -1G definition).
Time Synchronization IRIG-B, SNTP, PTP (IEEE 1588) support.
Operating Temperature -40°C to +70°C (Extended range, typical for -E version).
Mounting Panel-mounted.
Configuration Software ABB PCM600.
Typical Applications Protection of two-winding power transformers in:
• Utility transmission and distribution substations.
• Industrial plants (steel, cement, mining).
• Renewable energy plants (solar, wind farm step-up transformers).
• Data centers and critical infrastructure.