Technical Parameters
Category Specification
Product Series PSR - Digital Protection Relay
Device Type Modular Motor Management Relay / Intelligent Motor Protector
Key Standards IEC 60255, IEC 60947, ANSI/IEEE C37.90, IEC 61850 (with module)
Rated Auxiliary Supply 48–250 V DC / 48–240 V AC, 50/60 Hz (Auto-sensing, suffix -70)
Current Input (CT Secondary) 1 A or 5 A (Configurable, 1 A nominal shown by -600- code)
Measurement Accuracy Current: ±1% of reading; Voltage: ±0.5% of reading; Power: ±2% of reading
Core Protection Functions
• Thermal Model (49) Dual thermal models (running/stationary), adjustable overload curve, thermal alarm (e.g., 95%), trip (100%).
• Short Circuit (50/51) Phase instantaneous (I>) & time-delayed overcurrent (I>>) with IDMT/DT curves.
• Stall / Prolonged Start (48/14) Separate start thermal model, adjustable stall time setting.
• Phase Unbalance (46) Negative sequence protection (% of Iavg), trip delay.
• Earth Fault (50N/51N/67N) Residual (calculated) or core-balance (measured) current. Instantaneous or time-delayed, directional option.
• Underload / Jam (37) Minimum current or power protection.
• Under/Overvoltage (27/59) Two-stage with timers.
• Under/Overfrequency (81)
• Restart Inhibit / Starts per Hour Programmable number of starts and minimum time between starts.
Control & Logic
• Integrated PLC Engine Graphical logic editor (PSRsoft) for custom control sequences, interlocks, timers, counters.
• Pre-defined Control Profiles Direct-on-Line (DOL), Reversing, Star-Delta, Soft Starter, Pump, Valve, etc.
Inputs/Outputs (Base + Expandable)
• Binary Inputs (Discrete Inputs) 6 x 24-250V DC/AC programmable inputs (base unit). Expandable via I/O modules.
• Output Relays 5 x changeover (CO) relays (base unit: Trip, 2x Alarm, 2x Programmable). Expandable.
• Analog Inputs Optional module for 0/4-20 mA or PT100 temperature inputs.
Human-Machine Interface
• Display High-contrast graphical LCD with backlight (128 x 64 pixels).
• Indicators 10+ multi-color LEDs (Power, Ready, Run, Trip, Alarm, Comms, etc.).
• Navigation 6 tactile keys (Menu, Up, Down, Enter, Escape, Reset).
Monitoring & Diagnostics
• Measured Values Il1, Il2, Il3, Iavg, I_neg, I_earth, Vll, Vln, Freq, P, Q, S, PF, kWh, kVARh, Thermal Capacity, Starts Count, Run Hours.
• Event Recorder 512 time-stamped events (trips, alarms, commands, system events).
• Oscillography (Disturbance Recorder) 8 analog channels (currents/voltages), pre- and post-trigger recording.
Communication
• Front Port USB for local configuration (PSRsoft) and event log extraction.
• Rear Communication Slots 2 independent slots for plug-in modules:
- Protocols: Modbus RTU (RS485), Profibus DP, DeviceNet, IEC 61850, Modbus TCP/IP (Ethernet).
- I/O Expanders: Additional digital/analog I/O modules.
Clock & Synchronization Internal real-time clock; optional IRIG-B or SNTP (via comm module) for time sync.
Environmental
• Operating Temperature -25°C to +70°C
• Storage Temperature -40°C to +85°C
• Relative Humidity 5% to 95%, non-condensing
• Protection Rating IP40 (front), IP20 (terminals)
Mechanical
• Housing Self-extinguishing plastic (UL94 V-0), modular design.
• Mounting Panel-mounted (flush), requires cutout.
• Dimensions (W x H x D) 144 mm x 144 mm x 122 mm (6 TE width).
• Weight Approx. 1.2 kg (base unit).
Certifications CE, UL, cUL, DNV GL, ATEX (optional), IECEx (optional).