Parameter Category Specification
Product Family / Type Numerical Motor Protection and Control Relay (Motor Management System)
Standard Compliance IEC 60255, IEC 60947-1, -4, -5, IEC 61850 (with module)
Rated Auxiliary Supply Voltage (Us) 48 - 250 V DC / 48 - 240 V AC, 50/60 Hz (Auto-ranging, -70 suffix)
Motor Current Input (CT Secondary) 1 A or 5 A (Configurable)
Protection Functions
• Thermal Overload (49) Dual (separate) thermal models for Running and Stopped states. Includes cooling time constants, service factor, and bi-metallic compensation.
• Short Circuit / Instant OC (50) Instantaneous phase and earth-fault.
• Start-up Supervision / Stall (48/14) Anti-stall protection with separate thermal model for starts. Start time monitoring.
• Phase Unbalance & Loss (46) Negative sequence current protection with high sensitivity.
• Earth-Fault (50N/51N/67N) Directional or Non-directional, residual or core balance measurement. Multiple stages.
• Underload / Jam (37) Underpower or mechanical jam protection.
• Under/Overvoltage (27/59)
• Under/Overfrequency (81)
• Number of Starts Control of successive starts and restart inhibition time.
Control & Logic Features
• Integrated PLC Programmable logic (PSRsoft software) for custom control sequences, interlocking, and automation.
• Standard Control Profiles Direct-on-line (DOL), Star-Delta, Soft Starter, Pump, Valve control, etc.
• I/O Expansion Modular slots for additional digital/analog input & output modules.
Measured & Calculated Values Phase & ground currents, voltages, frequency, power (P, Q, S), power factor, energy, motor thermal capacity, starts counter, running hours.
Human-Machine Interface (HMI) Large backlit graphical LCD with status, measurements, bar graphs, event log. 6 navigation keys. 9+ LED indicators.
Event Logging & Oscillography Stores time-tagged fault records, alarms, operations. Optional disturbance recorder (oscillography) for pre-/post-fault current waveforms.
Output Contacts
• Base Unit Relays Typically 4-6 programmable changeover (CO) relays (Trip, Alarm, Control outputs).
• Expandable Via additional I/O modules.
Binary Inputs
• Base Unit Typically 4-6 programmable digital inputs.
• Expandable Via additional I/O modules (including analog inputs).
Communication (Standard & Optional)
• Standard Port RS485 (Modbus RTU protocol).
• Plug-in Modules Supports IEC 61850, Profibus DP, DeviceNet, Modbus TCP/IP (Ethernet), CANopen.
Operating Temperature -25°C to +60°C (-13°F to +140°F)
Housing & Mounting Modular plastic case for panel mounting. Width varies with configuration (base unit + modules).
Dimensions (Base Unit, W x H x D) Approximately 144mm x 144mm x 122mm (6TE width).