Parameter Category Specification
General Information
Product Series Eaton Commander C
Article Number / Model 130EMA-075CE22
Type Micro Drive, Variable Frequency Drive (VFD), AC Inverter
Enclosure Rating IP20 (Open Type). Must be installed in a suitable enclosure.
Standards CE, cULus, RoHS compliant. Designed to IEC/EN 61800 standards.
Power Characteristics
Rated Output Power 0.75 kW
Output Horsepower (HP) 1 HP
Input Supply (Mains) 1-Phase, 200-240V AC, 50/60 Hz
Output to Motor 3-Phase, 0-240V AC, 0-600 Hz (maximum)
Rated Output Current 3.8 A (This is the continuous current the drive can supply to the motor).
Overload Capacity 150% of rated current for 60 seconds, 200% for 3 seconds (typical).
Control & Performance
Control Methods V/f Control (Voltage/Frequency), Sensorless Vector Control (optional).
Frequency Reference Source Potentiometer (on keypad), analog input (0-10V, 0/4-20mA), preset speeds, Modbus communication.
Command Source Keypad (RUN/STOP), digital inputs, or serial communication.
Digital Inputs Typically 3 programmable digital inputs (sink/source).
Analog Input Typically 1 (programmable as 0-10V or 0/4-20mA).
Relay Output Typically 1 programmable relay output (changeover contact).
Analog Output Typically 1 (0-10V configurable).
Communication RS-485 Modbus RTU (standard). Optional cards for other networks (DeviceNet, Profibus).
Switching Frequency Adjustable (typically 2-16 kHz) to reduce motor noise or system losses.
Key Features Built-in DC bus choke, Auto-tuning (for motor parameter identification), multiple preset speeds, PID controller, braking transistor (for dynamic braking with external resistor), UL Type 1 kit option available.
Motor Connection
Recommended Motor Size 0.75 kW / 1 HP, 3-Phase, 230V AC induction motor.
Protection Functions Overcurrent, short-circuit, ground fault, overvoltage, undervoltage, motor overload (electronic thermal), drive overtemperature, loss of phase.
Physical & Environmental
Mounting DIN Rail (35mm) or panel mounting.
Dimensions (W x H x D) Approx. 55 x 146 x 136 mm (specific to frame size A).
Ambient Temperature -10°C to +50°C (derate above 40°C). -10°C to +40°C for full rated current (check manual).
Storage Temperature -40°C to +70°C.
Relative Humidity < 95% RH, non-condensing.
Altitude < 1000m without derating.