Products
Products
home
UR1BG3一030N-1KC-2SA一N

Yokogawa Temperature Transmitter (YTA Series), Model: UR1BG3-030N-1KC-2SA-N
This is a rail-mounted, two-wire temperature transmitter from Yokogawa's YTA series. It is designed for installation on a standard DIN rail within a control panel or cabinet. This model accepts an RTD (Pt100) sensor input and converts it into a standardized 4-20 mA analog output signal, proportional to the measured temperature, and incorporates HART® 7 protocol for digital communication and configuration.

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
Key Technical Parameters Summary
Input: RTD Pt100 (100Ω at 0°C, α=0.00385)

Range: -200 to 300 °C (can be limited and adjusted within this span)

Output: 4-20 mA DC, 2-wire system, with HART® 7 protocol

Power Supply: 12 to 42 V DC (standard loop power for 2-wire instruments)

Mounting: Standard DIN Rail (35 mm x 7.5 mm or 35 mm x 15 mm)

Ambient Temperature: -20 to 85 °C (-4 to 185 °F)

Electrical Connection: Spring clamp terminal block

Display: None

Safety Approvals (Primary):

ATEX/IECEx/UKCA: Ex ia IIC T6 Ga (Intrinsic Safety) / Ex nA IIC T6 Gc (Non-Incendive) Typical Applications
This rail-mounted transmitter is ideal for applications where:

Multiple transmitters need to be centralized in a control cabinet.

The sensor is located remotely from the measurement point.

The environment at the sensor location is too harsh for a head-mounted electronics unit.

Maintenance and configuration need to be performed in a centralized, protected location.

Important Note: