SCP401–11

The Yokogawa SCP401-11 is a highly versatile and compact Signal Conditioning Panel designed for centralized and high-density signal conditioning in industrial process control and monitoring systems. It acts as an interface between field devices (such as thermocouples, RTDs, strain gauges, analog transmitters, and contact signals) and the host system (like a Distributed Control System - DCS, Programmable Logic Controller - PLC, or data acquisition system).

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
Specifications
Category Specification Details
Model Yokogawa SCP401-11
Type Free-standing Signal Conditioning Panel (Floor Type)
Standard Conforms to JIS C 0904 (Degree of protection: IP00 for interior)
Enclosure Dimensions (H x W x D) 1600 mm x 600 mm x 400 mm (62.99" x 23.62" x 15.75")
Weight (Approx.) 80 kg (176.4 lbs)
Mounting Free-standing floor type
Cable Entry From top and bottom (Knockouts provided: 10 places of 35H, 10 places of 55H)
Wireway Dimensions (H x W) 60 mm x 400 mm (2.36" x 15.75")
Ambient Operating Temperature -10 to +55 °C (14 to 131 °F)
Ambient Operating Humidity 5 to 95 %RH (non-condensing)
Material Body: Steel plate (SPCC)
Surface Finish: Pretreatment + Melamine alkid resin baking paint (Color: Munsell 5Y7/1)
Internal Structure Panel: Steel plate (SPCC)
- Mounting surface for conditioners and terminal blocks
- Wireway with a removable cover
Power Supply 100 VAC, 50/60 Hz (Standard). Other voltages (115 VAC, 220 VAC, 240 VAC) available as an option.
Power Consumption Max. 500 VA (Depends on the number and type of conditioners installed)
Fuse Provided on the primary side of the power supply.
Installation Designed for installation in a controlled environment (e.g., panel room). Not rated for outdoor use.
Compatible Conditioners Accepts a wide range of Yokogawa SCP Series signal conditioners (e.g., for RTD, Thermocouple, mV, DC Voltage/Current, Contact Input, etc.).
Terminal Blocks Uses dedicated plug-in terminal blocks for simplified wiring and maintenance.
Key Features
High-Density Mounting: Allows for efficient use of panel room space.

Excellent Noise Immunity: Provides strong protection against electromagnetic interference (EMI) and ground loops, ensuring signal integrity.

Easy Wiring & Maintenance: Top and bottom cable entries and plug-in terminal blocks simplify installation and reduce maintenance time.

High Reliability & Safety: Built with industrial-grade components and includes electrical isolation and fusing for safe operation.

Scalability: The empty enclosure can be populated with various types of signal conditioners to meet the exact requirements of the application.