Products
Products
home
BMXAMI0800

The Schneider Electric BMXAMI0800 is an 8-channel analog input module designed for Modicon M340 PLC systems. It provides high-precision signal acquisition for various industrial sensors and transmitters, supporting both current and voltage inputs.

open

close

TEL:400-887-3214
Mail:jilineasyyi@outlook.com
Q Q:615739355
Parameters
Request a Quote
Return to List
Schneider Electric BMXAMI0800 Technical Specifications
General Parameters
Module Type: 8-Channel Analog Input Module

Compatible PLC: Modicon M340 Series

Mounting: DIN Rail (35mm)

Operating Temperature: -20°C to +60°C

Storage Temperature: -25°C to +70°C

Relative Humidity: 5% to 95% (non-condensing)

Vibration Resistance: 3.5mm amplitude (10-57Hz)

Shock Resistance: 15g (11ms duration)

Electrical Characteristics
Input Channels: 8 electrically isolated channels

Input Types:

Voltage: ±10V, 0-10V

Current: 0-20mA, 4-20mA (with HART protocol support)

Resolution: 16-bit

Accuracy:

±0.1% of full scale (voltage)

±0.2% of full scale (current)

Input Impedance:

1MΩ (voltage inputs)

250Ω (current inputs)

Sampling Rate: Configurable per channel (up to 10ms per channel)

Common Mode Rejection: >120dB at 50/60Hz

Normal Mode Rejection: >60dB at 50/60Hz

Isolation and Protection
Isolation:

600V between channels

600V between channels and backplane

Overvoltage Protection: ±30V continuous

Open Circuit Detection: Yes (for current inputs)

Short Circuit Protection: Yes (for current inputs)

Power Requirements
Backplane Power: 5V DC, 300mA max

Field Side Power: 24V DC (sensor supply)

Physical Characteristics
Dimensions (WxHxD): 45 x 118 x 117mm

Weight: 0.4kg

Connection Type: Removable screw terminal block

Wire Size: 0.2-2.5mm² (AWG 24-12)

Indicators
Per Channel LEDs: Green (active), Red (error)

Module Status LED: Green (OK), Red (Fault)

Certifications & Standards
Safety: UL 508, CSA C22.2 No.14

EMC: EN 61326-1, EN 61000-6-2, EN 61000-6-4

HART Protocol: Supported (for 4-20mA inputs)

RoHS: Compliant

Software Configuration
Configuration Tools: Unity Pro, EcoStruxure Control Expert

Programming: IEC 61131-3 compliant

Performance Data
Conversion Time: 1ms per channel (typical)

Update Rate: Configurable (1-10ms per channel)

Warm-up Time: <1 minute to specified accuracy

MTBF: >500,000 hours at 40°C

Environmental Compliance
IP Rating: IP20 (module), IP40 (installed in enclosure)

Altitude: 2000m max without derating

Typical Applications
Process variable monitoring (temperature, pressure, flow)

Analog sensor interfacing

Industrial automation systems

Energy management applications