General Parameters:
Model: ACS580-01-039A-4
Rated Power: 18.5 kW (25 HP)
Output Current: 39 A
Supply Voltage: 3-phase, 380–480 V AC (±10%)
Frequency Range: 48–63 Hz
Control Method: Sensorless Vector Control (DTC optional)
Enclosure: IP21 (standard), IP55 (optional)
Cooling Method: Air-cooled
Performance Features:
Speed Range: 1:10 (sensorless), 1:100 (with encoder)
Starting Torque: 150% at 0.5 Hz (sensorless)
Overload Capacity: 110% continuous, 150% for 60 sec
Switching Frequency: Default 4 kHz (adjustable up to 12 kHz)
Input/Output (I/O):
Digital Inputs: 6 (24 V DC, programmable)
Analog Inputs: 2 (0/4–20 mA or 0–10 V)
Relay Outputs: 2 (programmable, 250 V AC/30 V DC)
Analog Output: 1 (0/4–20 mA or 0–10 V)
Communication Options:
Built-in Protocols: Modbus RTU, BACnet MS/TP, Metasys N2
Optional Fieldbus: Profibus DP, Ethernet/IP, Modbus TCP/IP (via add-on modules)
Protection & Safety:
Protections: Overcurrent, overvoltage, undervoltage, motor overload, short circuit, ground fault, etc.
Safety Features: Safe Torque Off (STO) (optional)
Dimensions & Weight:
Width/Height/Depth: ~200 x 380 x 210 mm (varies by enclosure)
Weight: ~10–12 kg (depends on options)